Coefficient of Performance Calculator

Test cases replayed : 2 of 2 match · Methodology · No outside source listed

COP is the heat a heat pump delivers, or a refrigerator removes, per unit of work it uses. Enter both, plus the hot and cold temperatures.

Result

Sample figures

Coefficient of performance (COP)—

Same ratio in BTU per watt-hour —

  • Carnot (ideal) COP between the two temperatures—
  • Share of the Carnot limit reached—

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Coefficient of Performance Calculator

Machine: choose Heat pump (heating) or Refrigerator or air conditioner (cooling). Prefilled example: Heat pump (heating).

Heat delivered (heating) or removed (cooling), in kW: enter 0 or more. Prefilled example: 10.

Work or electric power used, in kW: enter 0 or more. Prefilled example: 3.

Temperature unit

Temperature unit: choose °F or °C. Prefilled example: °F.

Hot side temperature: enter a number. Prefilled example: 70.

Cold side temperature: enter a number. Prefilled example: 32.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Machine: choose Heat pump (heating) or Refrigerator or air conditioner (cooling).
  2. Heat delivered (heating) or removed (cooling), in kW: enter 0 or more.
  3. Work or electric power used, in kW: enter 0 or more.
  4. Temperature unit: choose °F or °C.
  5. Hot side temperature: enter a number.
  6. Cold side temperature: enter a number.
  7. Read the result: Coefficient of performance (COP); the panel also shows Same ratio in BTU per watt-hour, Carnot (ideal) COP between the two temperatures and Share of the Carnot limit reached.

How this calculator works

Heating COP = Q_H ÷ W and cooling COP = Q_C ÷ W, where Q is the heat moved and W the work (electric energy) used, in the same unit.

The second law of thermodynamics caps them at the Carnot values: COP_heat ≤ T_H ÷ (T_H − T_C) and COP_cool ≤ T_C ÷ (T_H − T_C), with temperatures in kelvin (°C + 273.15). A smaller temperature lift allows a higher COP.

Multiplying a COP by 3,600 ÷ 1,055.056 gives BTU per watt-hour, the unit of EER ratings (EER is measured at fixed test conditions). 1 BTU (IT) = 1,055.056 J (NIST SP 811, Appendix B, read October 27, 2026).

The formula

  1. Cop=qw
Symbols used in the formula
SymbolMeaningUnit
qHeat delivered (heating) or removed (cooling)kW
wWork or electric power usedkW
CopCoefficient of performance (COP)

Worked example

MachineHeat pump (heating)
Heat delivered (heating) or removed (cooling)10 kW
Work or electric power used3 kW
Temperature unit°F
Hot side temperature70
Cold side temperature32
Same ratio in BTU per watt-hour11.3738
Carnot (ideal) COP between the two temperatures13.9387
Share of the Carnot limit reached23.91%
  1. Cop=103=3.33333

Coefficient of performance (COP) 3.3333

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

Can a COP be greater than 1?

Yes. A heat pump moves heat rather than making it, so it can deliver several units of heat per unit of electricity.

What does a heat pump delivering 10 kW for 3 kW of power score?

A COP of about 3.3333.

Why does COP fall in cold weather?

The temperature gap between outdoors and indoors grows, and both the Carnot limit and real machines lose efficiency as it does.

Questions answered

Related calculators