Duct Size Calculator
Test cases replayed : 2 of 2 match · Methodology · No outside source listed
Enter the airflow the duct must carry and the air velocity you design for. You get the inside diameter of a round duct and the matching height of a rectangular duct for the width you have room for.
Result
Round duct inside diameterin
Free area needed (square inches)
- Rectangular duct height, same friction as the round duct (inches)
- Rectangular duct height, same area only (inches)
Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.
This browser did not allow copying. The sentence is in the box below, already selected: copy it with your keyboard or the menu.
Affiliate link
This is an affiliate link. As an Amazon Associate I earn from qualifying purchases. This does not change the result.
Search Amazon for HVAC ducts. Visit Amazon
How to use this calculator
Fill in the fields in this order; each step takes you to its field.
- Airflow (cubic feet per minute), in CFM: enter 1 or more.
- Design air velocity (feet per minute): enter 50 or more.
- Rectangular duct width, in in: enter 1 or more.
- Read the result: Round duct inside diameter; the panel also shows Free area needed (square inches), Rectangular duct height, same friction as the round duct (inches) and Rectangular duct height, same area only (inches).
How this calculator works
Velocity method: area (ft²) = CFM ÷ velocity (fpm); round diameter = √(4 × area ÷ π), converted to inches. Pick the next standard size up.
A rectangular duct carrying the same air with the same friction loss per foot has an equivalent diameter De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25 (Huebscher's 1948 equation). The calculator solves it for the height b at your width a.
A rectangle with the same area only has more friction than the round duct, so its height is shown for comparison but the same-friction height is the one to use.
Design velocities and friction rates come from a full duct design such as ACCA Manual D; this calculator sizes one run.
The formula
| Symbol | Meaning | Unit |
|---|---|---|
| Airflow | cubic feet per minute | |
| Design air velocity | feet per minute | |
| Round duct inside diameter | in |
Worked example
| Airflow (cubic feet per minute) | 400 CFM |
|---|---|
| Design air velocity (feet per minute) | 700 |
| Rectangular duct width | 10 in |
| Free area needed (square inches) | 82.3 |
|---|---|
| Rectangular duct height, same friction as the round duct (inches) | 8.8 |
| Rectangular duct height, same area only (inches) | 8.2 |
Round duct inside diameter 10.2 in
Each step uses the unrounded value of the step before it; figures on this page are rounded for display.
Frequently asked questions
Why is the rectangular duct larger in area than the round one?
A flat duct has more wall surface per unit of area, so it needs extra area to keep the same friction loss.
Is the diameter inside or outside?
Inside. Duct liner or insulation inside the duct reduces the free area; add its thickness.
How many CFM does a room need?
It comes from a room-by-room load calculation such as ACCA Manual J; this calculator starts from the airflow.