Electric Heater Size Calculator

Test cases replayed : 3 of 3 match · Methodology · No outside source listed

Enter the heat loss of the room at the coldest design temperature, the circuit voltage and the wattage of the heaters you are considering.

Result

Sample figures

Heater capacity needed—W

Heater capacity needed (kW) —

  • Current at full output (amps)—
  • Number of heaters of that wattage—
  • Cost per hour at full output—

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Electric Heater Size Calculator

Room heat loss at design temperature, in BTU/h: enter 0 or more. Prefilled example: 5,000.

Circuit voltage (V)

Circuit voltage (V): choose 120 V, 208 V or 240 V. Prefilled example: 240 V.

Wattage of one heater, in W: enter 1 or more. Prefilled example: 1,500.

Electricity price, in dollars / kWh: enter 0 or more. Prefilled example: 0.17.

Affiliate link

This is an affiliate link. As an Amazon Associate I earn from qualifying purchases. This does not change the result.

Search Amazon for electric space heaters. Visit Amazon

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Room heat loss at design temperature, in BTU/h: enter 0 or more.
  2. Circuit voltage (V): choose 120 V, 208 V or 240 V.
  3. Wattage of one heater, in W: enter 1 or more.
  4. Electricity price, in dollars / kWh: enter 0 or more.
  5. Read the result: Heater capacity needed; the panel also shows Heater capacity needed (kW), Current at full output (amps), Number of heaters of that wattage and Cost per hour at full output.

How this calculator works

An electric resistance heater turns all of the electricity it draws into heat, so its output in BTU per hour = watts × 3.412. Watts needed = heat loss ÷ 3.412, using the EIA conversion factor 1 kWh = 3,412 Btu.

Current (amps) = watts ÷ volts (P = V × I for a resistive load). Number of heaters = watts needed ÷ wattage of one heater, rounded up. Cost per hour at full output = kW × price per kWh; a thermostat runs the heater only part of the time, so the real cost per hour is lower in mild weather.

The room's heat loss can be estimated with the Heat Loss calculator from wall, window and ceiling areas, insulation and air leakage.

The formula

  1. W=hl3.412
Symbols used in the formula
SymbolMeaningUnit
hlRoom heat loss at design temperatureBTU/h
WHeater capacity neededW

Worked example

Room heat loss at design temperature5,000 BTU/h
Circuit voltage (V)240 V
Wattage of one heater1,500 W
Electricity price$0.17 / kWh
Heater capacity needed (kW)1.47
Current at full output (amps)6.1
Number of heaters of that wattage1
Cost per hour at full output$0.25
  1. W=5,0003.412=1,465.42

Heater capacity needed 1,465 W

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

How many watts does it take to heat a room?

As many as the room loses at the coldest expected temperature. A well-insulated room loses much less than a drafty one of the same size, so start from its heat loss rather than from floor area alone.

Should I use 120 V or 240 V?

Large baseboard and wall heaters usually run on 240 V, which draws half the current of 120 V for the same power. Wire size and breaker must match the circuit's current under the electrical code; have a licensed electrician size the circuit.

Is a 1,500 W heater enough?

A 1,500 W heater delivers about 5,118 BTU per hour (1,500 × 3.412). It is enough if the room's heat loss at design temperature is below that.