Skip to content
FiftyCalc Free calculators for all 50 states

EUI Calculator

Test cases replayed : 3 of 3 match · Methodology · No outside source listed

Enter twelve months of energy use from the utility bills and the building's gross floor area.

Result

Sample figures

Site EUI (kBtu/ft² per year)—

Annual site energy (kBtu) —

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

EUI Calculator

Electricity used in the year, in kWh: enter 0 or more. Prefilled example: 120,000.

Natural gas used in the year (therms): enter 0 or more. Prefilled example: 3,000.

Other fuels in the year (kBtu): enter 0 or more. Prefilled example: 0.

Gross floor area, in sq ft: enter 1 or more. Prefilled example: 10,000.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Electricity used in the year, in kWh: enter 0 or more.
  2. Natural gas used in the year (therms): enter 0 or more.
  3. Other fuels in the year (kBtu): enter 0 or more.
  4. Gross floor area, in sq ft: enter 1 or more.
  5. Read the result: Site EUI (kBtu/ft² per year); the panel also shows Annual site energy (kBtu).

How this calculator works

Site EUI = total annual site energy ÷ gross floor area. Each fuel is first converted to thousand Btu (kBtu) with the multipliers of ENERGY STAR Portfolio Manager: 1 kWh = 3.412 kBtu, 1 therm = 100 kBtu (natural gas billed in hundred cubic feet: 1 Ccf = 102.6 kBtu). Source: ENERGY STAR Portfolio Manager Technical Reference, Thermal Energy Conversions, August 2015 (https://portfoliomanager.energystar.gov/pdf/reference/Thermal%20Conversions.pdf, read 2026-10-27).

This is site energy, what the meters record. ENERGY STAR also reports source EUI, which adds the energy lost producing and delivering each fuel; compare buildings of the same type and climate.

The formula

  1. Kb=k×3.412+th×100+o
  2. Eui=Kba
Symbols used in the formula
SymbolMeaningUnit
kElectricity used in the yearkWh
thNatural gas used in the year (therms)
oOther fuels in the year (kBtu)
aGross floor areasq ft
KbAnnual site energy (kBtu)
EuiSite EUI (kBtu/ft² per year)

Worked example

Electricity used in the year120,000 kWh
Natural gas used in the year (therms)3,000
Other fuels in the year (kBtu)0
Gross floor area10,000 sq ft
Annual site energy (kBtu)709,440
  1. Kb=120,000×3.412+3,000×100+0=709,440
  2. Eui=709,44010,000=70.944

Site EUI (kBtu/ft² per year) 70.9

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

What is the EUI of a 10,000 ft² building using 120,000 kWh and 3,000 therms a year?

709,440 kBtu ÷ 10,000 ft² = 70.9 kBtu/ft² per year.

Is a lower EUI better?

For buildings of the same type and use, yes: it means less energy per square foot.