Skip to content
FiftyCalc Free calculators for all 50 states

Fan Laws Calculator

Test cases replayed : 2 of 2 match · Methodology · No outside source listed

Enter the fan's current airflow, pressure, power and speed, and the new speed.

Result

Sample figures

New airflow—CFM

Speed ratio N₂ ÷ N₁ —

  • New static pressure (in. of water)—
  • New shaft power (hp)—

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Fan Laws Calculator

Current airflow, in CFM: enter 0 or more. Prefilled example: 2,000.

Current static pressure (in. of water): enter 0 or more. Prefilled example: 0.5.

Current shaft power, in hp: enter 0 or more. Prefilled example: 0.5.

Current speed, in RPM: enter 0 or more. Prefilled example: 1,200.

New speed, in RPM: enter 0 or more. Prefilled example: 1,500.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Current airflow, in CFM: enter 0 or more.
  2. Current static pressure (in. of water): enter 0 or more.
  3. Current shaft power, in hp: enter 0 or more.
  4. Current speed, in RPM: enter 0 or more.
  5. New speed, in RPM: enter 0 or more.
  6. Read the result: New airflow; the panel also shows Speed ratio N₂ ÷ N₁, New static pressure (in. of water) and New shaft power (hp).

How this calculator works

Fan affinity laws for the same fan in the same system: airflow ∝ speed (Q₂ = Q₁ × N₂/N₁), pressure ∝ speed² (p₂ = p₁ × (N₂/N₁)²) and power ∝ speed³ (P₂ = P₁ × (N₂/N₁)³).

They assume constant air density and fan efficiency and an unchanged duct system, so they are a first estimate, not a substitute for the fan curve.

The formula

  1. R=n2n1
  2. Q2=q1×R
Symbols used in the formula
SymbolMeaningUnit
q1Current airflowCFM
n1Current speedRPM
n2New speedRPM
RSpeed ratio N₂ ÷ N₁
Q2New airflowCFM

Worked example

Current airflow2,000 CFM
Current static pressure (in. of water)0.5
Current shaft power0.5 hp
Current speed1,200 RPM
New speed1,500 RPM
Speed ratio N₂ ÷ N₁1.25
New static pressure (in. of water)0.7813
New shaft power (hp)0.9766
  1. R=1,5001,200=1.25
  2. Q2=2,000×1.25=2,500

New airflow 2,500 CFM

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

What happens to power if fan speed rises 25%?

It almost doubles: 1.25³ ≈ 1.95, so 0.5 hp becomes about 0.9766 hp.

Why does slowing a fan save so much energy?

Power falls with the cube of speed: at 80% speed the fan needs about 51.2% of the power.

Questions answered