Fan Laws Calculator
Test cases replayed : 2 of 2 match · Methodology · No outside source listed
Enter the fan's current airflow, pressure, power and speed, and the new speed.
Result
New airflowCFM
Speed ratio N₂ ÷ N₁
- New static pressure (in. of water)
- New shaft power (hp)
Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.
This browser did not allow copying. The sentence is in the box below, already selected: copy it with your keyboard or the menu.
How to use this calculator
Fill in the fields in this order; each step takes you to its field.
- Current airflow, in CFM: enter 0 or more.
- Current static pressure (in. of water): enter 0 or more.
- Current shaft power, in hp: enter 0 or more.
- Current speed, in RPM: enter 0 or more.
- New speed, in RPM: enter 0 or more.
- Read the result: New airflow; the panel also shows Speed ratio N₂ ÷ N₁, New static pressure (in. of water) and New shaft power (hp).
How this calculator works
Fan affinity laws for the same fan in the same system: airflow ∝ speed (Q₂ = Q₁ × N₂/N₁), pressure ∝ speed² (p₂ = p₁ × (N₂/N₁)²) and power ∝ speed³ (P₂ = P₁ × (N₂/N₁)³).
They assume constant air density and fan efficiency and an unchanged duct system, so they are a first estimate, not a substitute for the fan curve.
The formula
| Symbol | Meaning | Unit |
|---|---|---|
| Current airflow | CFM | |
| Current speed | RPM | |
| New speed | RPM | |
| Speed ratio N₂ ÷ N₁ | ||
| New airflow | CFM |
Worked example
| Current airflow | 2,000 CFM |
|---|---|
| Current static pressure (in. of water) | 0.5 |
| Current shaft power | 0.5 hp |
| Current speed | 1,200 RPM |
| New speed | 1,500 RPM |
| Speed ratio N₂ ÷ N₁ | 1.25 |
|---|---|
| New static pressure (in. of water) | 0.7813 |
| New shaft power (hp) | 0.9766 |
New airflow 2,500 CFM
Each step uses the unrounded value of the step before it; figures on this page are rounded for display.
Frequently asked questions
What happens to power if fan speed rises 25%?
It almost doubles: 1.25³ ≈ 1.95, so 0.5 hp becomes about 0.9766 hp.
Why does slowing a fan save so much energy?
Power falls with the cube of speed: at 80% speed the fan needs about 51.2% of the power.