Skip to content
FiftyCalc Free calculators for all 50 states

Furnace Size Calculator

Test cases replayed : 3 of 3 match · Methodology · No outside source listed

Enter the design heat loss of your home and the furnace efficiency. The furnace's heating output must cover the heat loss; its input rating is that output divided by the efficiency.

Result

Sample figures

Furnace input rating needed—BTU/h

Heating output capacity needed (BTU per hour) —

  • Heating output needed (kW)—

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Furnace Size Calculator

Design heat loss of the home, in BTU/h: enter 0 or more. Prefilled example: 48,000.

Furnace efficiency (close to its AFUE), in percent: enter a number from 50 to 100. Prefilled example: 95.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Design heat loss of the home, in BTU/h: enter 0 or more.
  2. Furnace efficiency (close to its AFUE), in percent: enter a number from 50 to 100.
  3. Read the result: Furnace input rating needed; the panel also shows Heating output capacity needed (BTU per hour) and Heating output needed (kW).

How this calculator works

A furnace is sized so that its heating output equals or slightly exceeds the home's heat loss at the outdoor design temperature. Output capacity = input rating × efficiency, so input rating = design heat loss ÷ efficiency. Example: 48,000 BTU/h ÷ 0.95 ≈ 50,526 BTU/h of input.

Furnace nameplates list both the input and the output (heating capacity) in BTU per hour; compare the output with your heat loss. AFUE is an annual efficiency that includes cycling losses, so the nameplate output is the more precise figure when you have it.

Heat loss is best taken from an ACCA Manual J load calculation by a contractor; the Heat Loss calculator gives an estimate from walls, windows, ceiling and air leakage. 1 kW = 3,412 BTU per hour (EIA conversion factor).

The formula

  1. I=hleff÷100
Symbols used in the formula
SymbolMeaningUnit
hlDesign heat loss of the homeBTU/h
effFurnace efficiency (close to its AFUE)%
IFurnace input rating neededBTU/h

Worked example

Design heat loss of the home48,000 BTU/h
Furnace efficiency (close to its AFUE)95%
Heating output capacity needed (BTU per hour)48,000
Heating output needed (kW)14.07
  1. I=48,00095÷100=50,526.32

Furnace input rating needed 50,526 BTU/h

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

Is a bigger furnace better?

No. An oversized furnace runs in short cycles, heats less evenly and wears faster. Choose the smallest standard size whose output covers the design heat loss.

What size furnace for a 2,000 square foot house?

It depends on climate, insulation and air leakage, not on floor area alone. Two homes of the same size can need very different furnaces, which is why the calculation starts from the heat loss.

Does altitude change furnace size?

Gas furnaces lose capacity at high altitude, so manufacturers give derating rules for installations above about 2,000 feet. Follow the installation manual of the model you choose.

Questions answered

Related calculators