Heat Loss Calculator
Test cases replayed : 2 of 2 match · Methodology · No outside source listed
Enter the areas and insulation values of the building envelope, the air changes per hour and the design temperatures.
Result
Total heat loss (BTU/h)
Temperature difference (°F)
- Walls (BTU/h)
- Windows and doors (BTU/h)
- Ceiling (BTU/h)
- Air leakage (BTU/h)
- Total heat loss (kW)
Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.
This browser did not allow copying. The sentence is in the box below, already selected: copy it with your keyboard or the menu.
How to use this calculator
Fill in the fields in this order; each step takes you to its field.
- Net wall area, in sq ft: enter 0 or more.
- Wall assembly R-value (h·ft²·°F/BTU): enter 0.1 or more.
- Window and door area, in sq ft: enter 0 or more.
- Window U-factor (BTU/h·ft²·°F): enter 0 or more.
- Ceiling area, in sq ft: enter 0 or more.
- Ceiling assembly R-value (h·ft²·°F/BTU): enter 0.1 or more.
- Heated volume, in cu ft: enter 0 or more.
- Air leakage (air changes per hour): enter 0 or more.
- Indoor temperature, in °F: enter a number.
- Outdoor design temperature, in °F: enter a number.
- Read the result: Total heat loss (BTU/h); the panel also shows Temperature difference (°F), Walls (BTU/h), Windows and doors (BTU/h), Ceiling (BTU/h), Air leakage (BTU/h) and Total heat loss (kW).
How this calculator works
Conduction through each surface: Q = U × A × ΔT, with U = 1 ÷ R. Q is in BTU per hour, A in square feet and ΔT the indoor minus outdoor temperature in °F.
Air leakage: Q = 0.018 × volume × ACH × ΔT. 0.018 BTU per cubic foot per °F is the heat capacity of air (0.075 lb/ft³ × 0.24 BTU/lb·°F), the value used in ASHRAE load methods.
This is a simple steady-state estimate. Floors, basements and duct losses are not included; equipment sizing in the US follows ACCA Manual J. 1 kW = 3,412.14 BTU/h.
The formula
| Symbol | Meaning | Unit |
|---|---|---|
| Net wall area | sq ft | |
| Wall assembly R-value (h·ft²·°F/BTU) | ||
| Window and door area | sq ft | |
| Window U-factor (BTU/h·ft²·°F) | ||
| Ceiling area | sq ft | |
| Ceiling assembly R-value (h·ft²·°F/BTU) | ||
| Heated volume | cu ft | |
| Air leakage (air changes per hour) | ||
| Indoor temperature | °F | |
| Outdoor design temperature | °F | |
| Temperature difference | °F | |
| Walls (BTU/h) | ||
| Windows and doors (BTU/h) | ||
| Ceiling (BTU/h) | ||
| Air leakage (BTU/h) | ||
| Total heat loss (BTU/h) |
Worked example
| Net wall area | 1,200 sq ft |
|---|---|
| Wall assembly R-value (h·ft²·°F/BTU) | 13 |
| Window and door area | 150 sq ft |
| Window U-factor (BTU/h·ft²·°F) | 0.3 |
| Ceiling area | 1,500 sq ft |
| Ceiling assembly R-value (h·ft²·°F/BTU) | 38 |
| Heated volume | 12,000 cu ft |
| Air leakage (air changes per hour) | 0.5 |
| Indoor temperature | 70 °F |
| Outdoor design temperature | 10 °F |
| Temperature difference (°F) | 60 |
|---|---|
| Walls (BTU/h) | 5,538 |
| Windows and doors (BTU/h) | 2,700 |
| Ceiling (BTU/h) | 2,368 |
| Air leakage (BTU/h) | 6,480 |
| Total heat loss (kW) | 5.01 |
Total heat loss (BTU/h) 17,087
Each step uses the unrounded value of the step before it; figures on this page are rounded for display.
Frequently asked questions
What is a design temperature?
The outdoor temperature a heating system is sized for, a cold value that is exceeded only a small share of hours in a typical winter; local values are published in ASHRAE climate data.
How does R-value change heat loss?
Heat loss through a surface is inversely proportional to R: doubling the R-value halves the loss through that surface.