Heat Loss Calculator

Test cases replayed : 2 of 2 match · Methodology · No outside source listed

Enter the areas and insulation values of the building envelope, the air changes per hour and the design temperatures.

Result

Sample figures

Total heat loss (BTU/h)—

Temperature difference (°F) —

  • Walls (BTU/h)—
  • Windows and doors (BTU/h)—
  • Ceiling (BTU/h)—
  • Air leakage (BTU/h)—
  • Total heat loss (kW)—

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Heat Loss Calculator

Net wall area, in sq ft: enter 0 or more. Prefilled example: 1,200.

Wall assembly R-value (h·ft²·°F/BTU): enter 0.1 or more. Prefilled example: 13.

Window and door area, in sq ft: enter 0 or more. Prefilled example: 150.

Window U-factor (BTU/h·ft²·°F): enter 0 or more. Prefilled example: 0.3.

Ceiling area, in sq ft: enter 0 or more. Prefilled example: 1,500.

Ceiling assembly R-value (h·ft²·°F/BTU): enter 0.1 or more. Prefilled example: 38.

Heated volume, in cu ft: enter 0 or more. Prefilled example: 12,000.

Air leakage (air changes per hour): enter 0 or more. Prefilled example: 0.5.

Indoor temperature, in °F: enter a number. Prefilled example: 70.

Outdoor design temperature, in °F: enter a number. Prefilled example: 10.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Net wall area, in sq ft: enter 0 or more.
  2. Wall assembly R-value (h·ft²·°F/BTU): enter 0.1 or more.
  3. Window and door area, in sq ft: enter 0 or more.
  4. Window U-factor (BTU/h·ft²·°F): enter 0 or more.
  5. Ceiling area, in sq ft: enter 0 or more.
  6. Ceiling assembly R-value (h·ft²·°F/BTU): enter 0.1 or more.
  7. Heated volume, in cu ft: enter 0 or more.
  8. Air leakage (air changes per hour): enter 0 or more.
  9. Indoor temperature, in °F: enter a number.
  10. Outdoor design temperature, in °F: enter a number.
  11. Read the result: Total heat loss (BTU/h); the panel also shows Temperature difference (°F), Walls (BTU/h), Windows and doors (BTU/h), Ceiling (BTU/h), Air leakage (BTU/h) and Total heat loss (kW).

How this calculator works

Conduction through each surface: Q = U × A × ΔT, with U = 1 ÷ R. Q is in BTU per hour, A in square feet and ΔT the indoor minus outdoor temperature in °F.

Air leakage: Q = 0.018 × volume × ACH × ΔT. 0.018 BTU per cubic foot per °F is the heat capacity of air (0.075 lb/ft³ × 0.24 BTU/lb·°F), the value used in ASHRAE load methods.

This is a simple steady-state estimate. Floors, basements and duct losses are not included; equipment sizing in the US follows ACCA Manual J. 1 kW = 3,412.14 BTU/h.

The formula

  1. Dt=tin−t
  2. W=wawr×Dt
  3. Wi=ga×gu×Dt
  4. C=cacr×Dt
  5. I=0.018×vol×ach×Dt
  6. To=W+Wi+C+I
Symbols used in the formula
SymbolMeaningUnit
waNet wall areasq ft
wrWall assembly R-value (h·ft²·°F/BTU)
gaWindow and door areasq ft
guWindow U-factor (BTU/h·ft²·°F)
caCeiling areasq ft
crCeiling assembly R-value (h·ft²·°F/BTU)
volHeated volumecu ft
achAir leakage (air changes per hour)
tinIndoor temperature°F
tOutdoor design temperature°F
DtTemperature difference°F
WWalls (BTU/h)
WiWindows and doors (BTU/h)
CCeiling (BTU/h)
IAir leakage (BTU/h)
ToTotal heat loss (BTU/h)

Worked example

Net wall area1,200 sq ft
Wall assembly R-value (h·ft²·°F/BTU)13
Window and door area150 sq ft
Window U-factor (BTU/h·ft²·°F)0.3
Ceiling area1,500 sq ft
Ceiling assembly R-value (h·ft²·°F/BTU)38
Heated volume12,000 cu ft
Air leakage (air changes per hour)0.5
Indoor temperature70 °F
Outdoor design temperature10 °F
Temperature difference (°F)60
Walls (BTU/h)5,538
Windows and doors (BTU/h)2,700
Ceiling (BTU/h)2,368
Air leakage (BTU/h)6,480
Total heat loss (kW)5.01
  1. Dt=70−10=60
  2. W=1,20013×60=5,538.46
  3. Wi=150×0.3×60=2,700
  4. C=1,50038×60=2,368.42
  5. I=0.018×12,000×0.5×60=6,480
  6. To=5,538.46+2,700+2,368.42+6,480=17,086.88

Total heat loss (BTU/h) 17,087

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

What is a design temperature?

The outdoor temperature a heating system is sized for, a cold value that is exceeded only a small share of hours in a typical winter; local values are published in ASHRAE climate data.

How does R-value change heat loss?

Heat loss through a surface is inversely proportional to R: doubling the R-value halves the loss through that surface.

Questions answered