Mixed Air Calculator

Test cases replayed : 2 of 2 match · Methodology · No outside source listed

Use three temperatures measured at an air handler to find what share of the supply air is outdoor air.

Result

Sample figures

Outdoor air—

Outdoor airflow (CFM) —

  • Return airflow (CFM)—

The unit choice applies to the fields you fill in. Results stay in the units written with them.

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Mixed Air Calculator

Units: switches the fields between the two unit systems.

Outdoor air temperature, in °F: enter a number. Prefilled example: 90.

Return air temperature, in °F: enter a number. Prefilled example: 75.

Mixed air temperature, in °F: enter a number. Prefilled example: 78.

Total supply airflow, in CFM: enter 0 or more. Prefilled example: 10,000.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Units: switches the fields between the two unit systems.
  2. Outdoor air temperature, in °F: enter a number.
  3. Return air temperature, in °F: enter a number.
  4. Mixed air temperature, in °F: enter a number.
  5. Total supply airflow, in CFM: enter 0 or more.
  6. Read the result: Outdoor air; the panel also shows Outdoor airflow (CFM) and Return airflow (CFM).

How this calculator works

Sensible mixing balance: the mixed air temperature is the flow-weighted average of outdoor and return air, so the outdoor air fraction is %OA = (T_return − T_mixed) ÷ (T_return − T_outdoor) × 100.

This temperature method is used in testing and balancing; it gets unreliable when the outdoor and return temperatures are close together, or when the mixed air is stratified. Any temperature scale works, as long as all three use the same one.

The formula

  1. Oa=tr−tmtr−to×100
Symbols used in the formula
SymbolMeaningUnit
toOutdoor air temperature°F
trReturn air temperature°F
tmMixed air temperature°F
OaOutdoor air%

Worked example

Outdoor air temperature90 °F
Return air temperature75 °F
Mixed air temperature78 °F
Total supply airflow10,000 CFM
Outdoor airflow (CFM)2,000
Return airflow (CFM)8,000
  1. Oa=75−7875−90×100=20

Outdoor air 20%

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

Why measure outdoor air percentage?

To check that an air handler brings in the ventilation air it was designed for, and that its economizer dampers work.

What if the mixed temperature is outside the other two?

The reading is wrong (stratification or a bad sensor): the mixed temperature must lie between the outdoor and return temperatures.