Mixed Air Temperature Calculator

Test cases replayed : 2 of 2 match · Methodology · No outside source listed

Find the temperature you get when two airstreams mix, such as outdoor air and return air in an air handler.

Result

Sample figures

Mixed air temperature—°F

Mixed air temperature (°C) —

  • Total airflow (CFM)—
  • Share of airflow 1 (%)—

The unit choice applies to the fields you fill in. Results stay in the units written with them.

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Mixed Air Temperature Calculator

Units: switches the fields between the two unit systems.

Airflow 1, e.g. outdoor air, in CFM: enter 0 or more. Prefilled example: 2,000.

Temperature 1, in °F: enter a number. Prefilled example: 95.

Airflow 2, e.g. return air, in CFM: enter 0 or more. Prefilled example: 8,000.

Temperature 2, in °F: enter a number. Prefilled example: 75.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Units: switches the fields between the two unit systems.
  2. Airflow 1, e.g. outdoor air, in CFM: enter 0 or more.
  3. Temperature 1, in °F: enter a number.
  4. Airflow 2, e.g. return air, in CFM: enter 0 or more.
  5. Temperature 2, in °F: enter a number.
  6. Read the result: Mixed air temperature; the panel also shows Mixed air temperature (°C), Total airflow (CFM) and Share of airflow 1 (%).

How this calculator works

Sensible heat balance for adiabatic mixing: T_mix = (Q₁ × T₁ + Q₂ × T₂) ÷ (Q₁ + Q₂), the airflow-weighted average of the two temperatures.

It treats both streams as having the same density and specific heat, which is close enough for usual HVAC temperatures; for very different temperatures, weight by mass flow instead. °C = (°F − 32) ÷ 1.8.

The formula

  1. Tm=q1×t1+q2×t2q1+q2
Symbols used in the formula
SymbolMeaningUnit
q1Airflow 1, e.g. outdoor airCFM
t1Temperature 1°F
q2Airflow 2, e.g. return airCFM
t2Temperature 2°F
TmMixed air temperature°F

Worked example

Airflow 1, e.g. outdoor air2,000 CFM
Temperature 195 °F
Airflow 2, e.g. return air8,000 CFM
Temperature 275 °F
Mixed air temperature (°C)26.1111
Total airflow (CFM)10,000
Share of airflow 1 (%)20%
  1. Tm=2,000×95+8,000×752,000+8,000=79

Mixed air temperature 79 °F

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

What is the mix of 20% outdoor air at 95 °F with return air at 75 °F?

79 °F.

Does the mixed air humidity follow the same rule?

The humidity ratio mixes the same way (flow-weighted), but relative humidity does not, because it depends on temperature.