The ε-NTU method rates a heat exchanger without knowing the outlet temperatures. Enter the NTU, the capacity ratio, the flow arrangement and the inlet data.
Result
Effectiveness ε
Heat transfer rate (kW)
Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.
This browser did not allow copying. The sentence is in the box below, already selected: copy it with your keyboard or the menu.
How to use this calculator
Fill in the fields in this order; each step takes you to its field.
- Number of transfer units NTU = UA ÷ C_min: enter 0 or more.
- Capacity ratio C_r = C_min ÷ C_max: enter a number from 0 to 1.
- Flow arrangement: choose Counterflow or Parallel flow.
- C_min = (m × cp) of the weaker stream (W/K): enter 0 or more.
- Hot inlet temperature, in °C: enter a number.
- Cold inlet temperature, in °C: enter a number.
- Read the result: Effectiveness ε; the panel also shows Heat transfer rate (kW).
How this calculator works
Effectiveness ε = q ÷ q_max with q_max = C_min (T_h,in − T_c,in). Counterflow: ε = (1 − e^(−NTU(1−Cr))) ÷ (1 − Cr e^(−NTU(1−Cr))), or NTU ÷ (1 + NTU) when Cr = 1. Parallel flow: ε = (1 − e^(−NTU(1+Cr))) ÷ (1 + Cr). These are the standard relations from Kays and London, Compact Heat Exchangers.
NTU = U A ÷ C_min, with U the overall heat transfer coefficient and A the area; C = mass flow × specific heat for each stream.
Worked example
| Number of transfer units NTU = UA ÷ C_min | 2 |
|---|---|
| Capacity ratio C_r = C_min ÷ C_max | 0.5 |
| Flow arrangement | Counterflow |
| C_min = (m × cp) of the weaker stream (W/K) | 2,000 |
| Hot inlet temperature | 90 °C |
| Cold inlet temperature | 20 °C |
| Effectiveness ε | 77.46% |
|---|---|
| Heat transfer rate (kW) | 108.444 |
Frequently asked questions
Why is counterflow more effective?
The cold fluid leaves next to the hot inlet, so it can approach the hottest temperature; with NTU = 2 and Cr = 0.5 counterflow gives about 77.46% against 63.35% for parallel flow.
What is the limit of parallel flow?
Even with infinite area, its effectiveness cannot exceed 1 ÷ (1 + Cr).