Heat Transfer Coefficient Calculator
Test cases replayed : 2 of 2 match · Methodology · No outside source listed
Enter the convective coefficient on each side and the wall thickness and conductivity. Add the area and temperature difference for the heat flow.
Result
U-value (W/(m²·K))
Total thermal resistance (m²·K/W)
- U-factor (BTU/(h·ft²·°F))
- Heat flow (W)
Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.
This browser did not allow copying. The sentence is in the box below, already selected: copy it with your keyboard or the menu.
How to use this calculator
Fill in the fields in this order; each step takes you to its field.
- Inside film coefficient h₁ (W/(m²·K)): enter 0 or more.
- Wall thickness, in mm: enter 0 or more.
- Wall conductivity k (W/(m·K)): enter 0 or more.
- Outside film coefficient h₂ (W/(m²·K)): enter 0 or more.
- Area, in m²: enter 0 or more.
- Temperature difference (K or °C): enter a number.
- Read the result: U-value (W/(m²·K)); the panel also shows Total thermal resistance (m²·K/W), U-factor (BTU/(h·ft²·°F)) and Heat flow (W).
How this calculator works
For a plane wall the resistances add in series: 1 ÷ U = 1 ÷ h₁ + d ÷ k + 1 ÷ h₂. The heat flow is Q̇ = U A ΔT.
1 BTU/(h·ft²·°F) = 5.678263 W/(m²·K) (NIST Special Publication 811, Appendix B.9 (https://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9, read 2026-10-27)). The R-value used in US building codes is the reciprocal of the U-factor in US units.
The formula
| Symbol | Meaning | Unit |
|---|---|---|
| Inside film coefficient h₁ (W/(m²·K)) | ||
| Wall thickness | mm | |
| Wall conductivity k (W/(m·K)) | ||
| Outside film coefficient h₂ (W/(m²·K)) | ||
| Total thermal resistance | m²·K/W | |
| U-value (W/(m²·K)) |
Worked example
| Inside film coefficient h₁ (W/(m²·K)) | 10 |
|---|---|
| Wall thickness | 200 mm |
| Wall conductivity k (W/(m·K)) | 0.8 |
| Outside film coefficient h₂ (W/(m²·K)) | 25 |
| Area | 20 m² |
| Temperature difference (K or °C) | 20 |
| Total thermal resistance (m²·K/W) | 0.39 |
|---|---|
| U-factor (BTU/(h·ft²·°F)) | 0.4516 |
| Heat flow (W) | 1025.6 |
U-value (W/(m²·K)) 2.5641
Each step uses the unrounded value of the step before it; figures on this page are rounded for display.
Frequently asked questions
What U-value do h₁ = 10, h₂ = 25 and 200 mm of k = 0.8 give?
About 2.5641 W/(m²·K): the resistances 0.1 + 0.25 + 0.04 sum to 0.39 m²·K/W.
Which layer matters most?
The largest resistance. Here the wall itself (0.25 m²·K/W) dominates the two films.