Skip to content
FiftyCalc Free calculators for all 50 states

Sensible Heat Calculator

Test cases replayed : 2 of 2 match · Methodology · No outside source listed

Enter the airflow and the temperature difference across a coil or a room to get the sensible heat load.

Result

Sample figures

Sensible heat (Btu/h)—

Air factor 60 × ρ × cp —

  • Sensible heat (kW)—
  • Sensible heat (tons of refrigeration)—

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Sensible Heat Calculator

Airflow (ft³/min), in CFM: enter 0 or more. Prefilled example: 1,000.

Temperature difference ΔT, in °F: enter 0 or more. Prefilled example: 20.

Air density (lb/ft³), example value for standard air: enter 0 or more. Prefilled example: 0.075.

Specific heat of air (Btu/lb·°F), example value: enter 0 or more. Prefilled example: 0.24.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Airflow (ft³/min), in CFM: enter 0 or more.
  2. Temperature difference ΔT, in °F: enter 0 or more.
  3. Air density (lb/ft³), example value for standard air: enter 0 or more.
  4. Specific heat of air (Btu/lb·°F), example value: enter 0 or more.
  5. Read the result: Sensible heat (Btu/h); the panel also shows Air factor 60 × ρ × cp, Sensible heat (kW) and Sensible heat (tons of refrigeration).

How this calculator works

Q = 60 × ρ × cp × CFM × ΔT, the sensible heat equation for air: 60 min/h × density × specific heat × airflow × temperature change. With 0.075 lb/ft³ and 0.24 Btu/(lb·°F) the factor is 1.08, the familiar Q = 1.08 × CFM × ΔT.

Density and specific heat are editable: change them for altitude or hot air. 1 Btu/h = 0.2930711 W and 1 ton of refrigeration = 12,000 Btu/h (NIST SP 811, Appendix B.9 conversion factors, read on nist.gov on 2026-10-27).

The formula

  1. K=60×ρ×cp
  2. Q=K×cfm×dt
Symbols used in the formula
SymbolMeaningUnit
cfmAirflow (ft³/min)CFM
dtTemperature difference ΔT°F
ρAir density (lb/ft³), example value for standard air
cpSpecific heat of air (Btu/lb·°F), example value
KAir factor 60 × ρ × cp
QSensible heat (Btu/h)

Worked example

Airflow (ft³/min)1,000 CFM
Temperature difference ΔT20 °F
Air density (lb/ft³), example value for standard air0.075
Specific heat of air (Btu/lb·°F), example value0.24
Air factor 60 × ρ × cp1.08
Sensible heat (kW)6.3303
Sensible heat (tons of refrigeration)1.8
  1. K=60×0.075×0.24=1.08
  2. Q=1.08×1,000×20=21,600

Sensible heat (Btu/h) 21,600

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

What is sensible heat?

Heat that changes the air's temperature, as opposed to latent heat, which changes its moisture content.

How many BTU/h do 1,000 CFM carry at a 20 °F rise?

21,600 Btu/h with the 1.08 factor, about 6.33 kW or 1.8 tons.

Related calculators