Power Factor Calculator
Test cases replayed : 2 of 2 match · Methodology · Sources
Find power factor from measured real power, voltage and current.
Result
Power factor
Apparent power (kVA)
Reading the result
At a glance
What moves the result
Method and sources: How this calculator works, Sources
- Phase angle (degrees)
- Reactive power (kVAR)
Estimate for planning only, not tax, legal, financial or medical advice. Check important figures with the official source listed on this page.
This browser did not allow copying. The sentence is in the box below, already selected: copy it with your keyboard or the menu.
How to use this calculator
Fill in the fields in this order; each step takes you to its field.
- Real power, in kW: enter 0 or more.
- Voltage (line-to-line for three-phase), in V: enter 0 or more.
- Current, in A: enter 0 or more.
- Circuit: choose Single-phase or Three-phase.
- Read the result: Power factor; the panel also shows Apparent power (kVA), Phase angle (degrees) and Reactive power (kVAR).
Sources
- Reducing Power Factor Cost U.S. Department of Energy, Motor Challenge checked on 2026-11-02
How this calculator works
Apparent power S = V × I (single-phase) or √3 × V × I (three-phase). Power factor = real power P ÷ S; phase angle = arccos(PF); reactive power Q = √(S² − P²).
A power factor above 1 means the inputs do not match a real measurement, and the angle shows a dash.
The formula
| Symbol | Meaning | Unit |
|---|---|---|
| Real power | kW | |
| Voltage (line-to-line for three-phase) | V | |
| Current | A | |
| Circuit | ||
| Apparent power (kVA) | ||
| Power factor |
Worked example
| Real power | 8 kW |
|---|---|
| Voltage (line-to-line for three-phase) | 240 V |
| Current | 40 A |
| Circuit | Single-phase |
| Apparent power (kVA) | 9.6 |
|---|---|
| Phase angle (degrees) | 33.5573 |
| Reactive power (kVAR) | 5.3066 |
Power factor 0.8333
Each step uses the unrounded value of the step before it; figures on this page are rounded for display.
Frequently asked questions
What is a good power factor?
Close to 1. Many utilities charge an additional fee when the power factor is below 0.95.
What causes a low power factor?
Inductive loads such as motors and transformers, which draw reactive current.