Enter the current measured on each line. The calculator adds them as phasors to give the current that returns on the neutral.

Result

Sample figures

Neutral current—A

Estimate for planning only, not tax, legal, financial or medical advice. This calculator uses the method explained on this page.

Neutral Current Calculator

System: choose Three-phase four-wire wye (phases 120° apart) or Single-phase three-wire 120/240 V (split-phase). Prefilled example: Three-phase four-wire wye (phases 120° apart).

Line A (or L1) current, in A: enter 0 or more. Prefilled example: 100.

Line B (or L2) current, in A: enter 0 or more. Prefilled example: 80.

Line C current, three-phase only, in A: enter 0 or more. Prefilled example: 60.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. System: choose Three-phase four-wire wye (phases 120° apart) or Single-phase three-wire 120/240 V (split-phase).
  2. Line A (or L1) current, in A: enter 0 or more.
  3. Line B (or L2) current, in A: enter 0 or more.
  4. Line C current, three-phase only, in A: enter 0 or more.
  5. Read the result: Neutral current.

How this calculator works

By Kirchhoff's current law, the neutral carries the phasor sum of the line currents. In a wye system the three currents are 120° apart; with loads of the same power factor on each phase, the sum reduces to I_N = √(I_A² + I_B² + I_C² − I_A·I_B − I_B·I_C − I_C·I_A).

In a 120/240 V split-phase system the two lines are 180° apart, so the neutral carries the difference of the two line currents, I_N = |I_L1 − I_L2|. The line C field is not used.

Assumptions: linear loads with the same power factor on every phase. Harmonic currents from electronic loads (multiples of the third harmonic) add in the neutral instead of cancelling and are not included; size conductors under the National Electrical Code with a licensed electrician.

The formula

  1. N={ia2+ib2+ic2−ia×ib−ib×ic−ic×iaif sw≠0|ia−ib|otherwise
Symbols used in the formula
SymbolMeaningUnit
iaLine A (or L1) currentA
ibLine B (or L2) currentA
icLine C current, three-phase onlyA
swOne if System is Three-phase four-wire wye (phases 120° apart), zero otherwise
NNeutral currentA

Worked example

SystemThree-phase four-wire wye (phases 120° apart)
Line A (or L1) current100 A
Line B (or L2) current80 A
Line C current, three-phase only60 A
  1. N=1002+802+602−100×80−80×60−60×100=34.641

Neutral current 34.641 A

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

Why is the neutral current zero when the phases are balanced?

Three equal currents 120° apart cancel exactly. With 50 A on each phase the formula gives 50² × 3 − 50² × 3 = 0.

Can the neutral current exceed the phase currents?

Not with linear loads of equal power factor; it is at most the largest line current, reached for example when only one phase is loaded, or when two phases carry the same current and the third none. Harmonic currents are outside this formula.

Does this work for a 120/208 V system?

Yes, a 120/208 V system is a three-phase four-wire wye; use the three-phase choice.