Skip to content
FiftyCalc Free calculators for all 50 states

Wire Gauge Calculator

Test cases replayed : 3 of 3 match · Methodology · Sources

Pick an AWG size to get its diameter, cross-section area and the resistance of annealed copper wire of that size.

Result

Sample figures

Area—mm²

Diameter (inches) —

  • Diameter (mm)—
  • Area (kcmil)—
  • Copper resistance at 20 °C (ohms per 1,000 ft)—
  • Copper resistance at 20 °C (ohms per km)—

Estimate for planning only, not tax, legal, financial or medical advice. Check important figures with the official source listed on this page.

Wire Gauge Calculator

Wire size (AWG): choose one of the 44 options in the list. Prefilled example: 12.

Affiliate link

This is an affiliate link. As an Amazon Associate I earn from qualifying purchases. This does not change the result.

Search Amazon for electrical wire. Visit Amazon

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Wire size (AWG): choose one of the 44 options in the list.
  2. Read the result: Area; the panel also shows Diameter (inches), Diameter (mm), Area (kcmil), Copper resistance at 20 °C (ohms per 1,000 ft) and Copper resistance at 20 °C (ohms per km).

Sources

How this calculator works

The American Wire Gauge is a geometric series: No. 0000 is 0.4600 in and No. 36 is 0.0050 in, with 38 steps between, so d(n) = 0.005 in × 92^((36 − n)/39) (NIST Handbook 100, Copper Wire Tables, nvlpubs.nist.gov, read October 27, 2026). Sizes 0000 to 0 are entered as −3 to 0.

Area in circular mils = (diameter in mils)²; 1 mil = 0.001 in. Resistance uses the International Annealed Copper Standard, 10.371 Ω·cmil/ft at 20 °C (same handbook). Published tables round diameters to 0.1 mil, so the last digit can differ slightly.

The formula

  1. Din=0.005×92(36−g)÷39
  2. Mm2=π4×(Din×25.4)2
Symbols used in the formula
SymbolMeaningUnit
gWire size (AWG)
DinDiameterinches
Mm2Areamm²

Worked example

Wire size (AWG)12
Diameter (inches)0.0808
Diameter (mm)2.0525
Area (kcmil)6.5299
Copper resistance at 20 °C (ohms per 1,000 ft)1.5882
Copper resistance at 20 °C (ohms per km)5.2107
  1. Din=0.005×92(36−12)÷39=0.0808081
  2. Mm2=3.141594×(0.0808081×25.4)2=3.30877

Area 3.3088 mm²

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

What is the diameter of 12 AWG wire?

About 0.0808 in (2.053 mm), with an area of about 3.31 mm².

Does a bigger gauge number mean a thicker wire?

No, the opposite: every 6 gauge numbers the diameter halves, and every 3 numbers the area roughly halves.