Wire Resistance Calculator

Test cases replayed : 2 of 2 match · Methodology · Sources

Pick the wire size, enter its length and temperature to get its resistance.

Result

Sample figures

Wire resistance—Ω

Resistance per 1,000 ft (ohms) —

Estimate for planning only, not tax, legal, financial or medical advice. Check important figures with the official source listed on this page.

Wire Resistance Calculator

Wire size (AWG): choose one of the 44 options in the list. Prefilled example: 14.

Length unit

Length unit: choose feet or meters. Prefilled example: feet.

Wire length (one conductor): enter 0 or more. Prefilled example: 100.

Conductivity (% IACS; 100 = annealed copper, 97.5 = hard-drawn copper): enter a number from 1 to 110. Prefilled example: 100.

Wire temperature, in °C: enter a number from -100 to 200. Prefilled example: 20.

How to use this calculator

Fill in the fields in this order; each step takes you to its field.

  1. Wire size (AWG): choose one of the 44 options in the list.
  2. Length unit: choose feet or meters.
  3. Wire length (one conductor): enter 0 or more.
  4. Conductivity (% IACS; 100 = annealed copper, 97.5 = hard-drawn copper): enter a number from 1 to 110.
  5. Wire temperature, in °C: enter a number from -100 to 200.
  6. Read the result: Wire resistance; the panel also shows Resistance per 1,000 ft (ohms).

Sources

How this calculator works

R = ρ L / A. The International Annealed Copper Standard gives 10.371 Ω per circular-mil-foot at 20 °C (0.017241 Ω·mm²/m), a temperature coefficient of 0.00393 per °C at 20 °C, and the rule that the coefficient is proportional to conductivity; hard-drawn copper is taken as 97.5% IACS (NIST Handbook 100, Copper Wire Tables, nvlpubs.nist.gov, read October 27, 2026).

Area comes from the AWG definition d = 0.005 in × 92^((36 − n)/39); 1 m = 3.280839895 ft (0.3048 m per ft). For a circuit, use the out-and-back length of both conductors.

The formula

  1. Rpk=10.371(0.005×92(36−g)÷39×1,000)2×i÷100×1,000×(1+0.00393×i100×(t−20))
  2. R=Rpk×len×lu1,000
Symbols used in the formula
SymbolMeaningUnit
gWire size (AWG)
luLength unit
lenWire length (one conductor)
iConductivity (% IACS; 100 = annealed copper, 97.5 = hard-drawn copper)
tWire temperature°C
RpkResistance per 1,000 ftohms
RWire resistanceΩ

Worked example

Wire size (AWG)14
Length unitfeet
Wire length (one conductor)100
Conductivity (% IACS; 100 = annealed copper, 97.5 = hard-drawn copper)100
Wire temperature20 °C
Resistance per 1,000 ft (ohms)2.5254
  1. Rpk=10.371(0.005×92(36−14)÷39×1,000)2×100÷100×1,000×(1+0.00393×100100×(20−20))=2.52537
  2. R=2.52537×100×11,000=0.252537

Wire resistance 0.2525 Ω

Each step uses the unrounded value of the step before it; figures on this page are rounded for display.

Frequently asked questions

What is the resistance of 100 ft of 14 AWG copper?

About 0.25 Ω at 20 °C (2.525 Ω per 1,000 ft).

How much does heat increase resistance?

For annealed copper about 0.393% per °C: a wire at 70 °C has about 20% more resistance than at 20 °C.