Wire Resistance Calculator
Test cases replayed : 2 of 2 match · Methodology · Sources
Pick the wire size, enter its length and temperature to get its resistance.
Result
Wire resistanceΩ
Resistance per 1,000 ft (ohms)
Reading the result
At a glance
What moves the result
Method and sources: How this calculator works, Sources
Estimate for planning only, not tax, legal, financial or medical advice. Check important figures with the official source listed on this page.
This browser did not allow copying. The sentence is in the box below, already selected: copy it with your keyboard or the menu.
How to use this calculator
Fill in the fields in this order; each step takes you to its field.
- Wire size (AWG): choose one of the 44 options in the list.
- Length unit: choose feet or meters.
- Wire length (one conductor): enter 0 or more.
- Conductivity (% IACS; 100 = annealed copper, 97.5 = hard-drawn copper): enter a number from 1 to 110.
- Wire temperature, in °C: enter a number from -100 to 200.
- Read the result: Wire resistance; the panel also shows Resistance per 1,000 ft (ohms).
Sources
- NBS Handbook 100, Copper Wire Tables National Bureau of Standards (NIST) checked on 2026-11-01
How this calculator works
R = ρ L / A. The International Annealed Copper Standard gives 10.371 Ω per circular-mil-foot at 20 °C (0.017241 Ω·mm²/m), a temperature coefficient of 0.00393 per °C at 20 °C, and the rule that the coefficient is proportional to conductivity; hard-drawn copper is taken as 97.5% IACS (NIST Handbook 100, Copper Wire Tables, nvlpubs.nist.gov, read October 27, 2026).
Area comes from the AWG definition d = 0.005 in × 92^((36 − n)/39); 1 m = 3.280839895 ft (0.3048 m per ft). For a circuit, use the out-and-back length of both conductors.
The formula
| Symbol | Meaning | Unit |
|---|---|---|
| Wire size (AWG) | ||
| Length unit | ||
| Wire length (one conductor) | ||
| Conductivity (% IACS; 100 = annealed copper, 97.5 = hard-drawn copper) | ||
| Wire temperature | °C | |
| Resistance per 1,000 ft | ohms | |
| Wire resistance | Ω |
Worked example
| Wire size (AWG) | 14 |
|---|---|
| Length unit | feet |
| Wire length (one conductor) | 100 |
| Conductivity (% IACS; 100 = annealed copper, 97.5 = hard-drawn copper) | 100 |
| Wire temperature | 20 °C |
| Resistance per 1,000 ft (ohms) | 2.5254 |
|---|
Wire resistance 0.2525 Ω
Each step uses the unrounded value of the step before it; figures on this page are rounded for display.
Frequently asked questions
What is the resistance of 100 ft of 14 AWG copper?
About 0.25 Ω at 20 °C (2.525 Ω per 1,000 ft).
How much does heat increase resistance?
For annealed copper about 0.393% per °C: a wire at 70 °C has about 20% more resistance than at 20 °C.